Wires and Cables for Machine Internal

Product name

KIV/HKIV PVC insulated wires for electrical equipment

icon-pse.svg icon-pse.svg Product symbols

Applications

  • Used as wiring for electrical equipment and control panels operating at 600 V or less.

Features

  • Flexible stranded wires are used as the conductor, for excellent flexibility.
  • HKIV uses tin-plated soft annealed copper wires (TA) as the conductor, for excellent soldering performance and corrosion resistance.
  • Sizes 0.5–5.5 mm²: Each bundle comes in an individual case.
  • Sizes 8–14 mm²: Paper wrapping

Structural diagram

Surface marking

Insulator standard colors

The basic 6 colors are black, white, red, green, yellow, and blue. Other colors are also available.

Precautions for use

The basic 6 colors are black, white, red, green, yellow, and blue. Other colors are also available.

Structural table

Conductor
Conductor
Insulator
Thickness
Insulator
thickness
mm
Finished
Outer diameter
Finished outer diameter
mm
Conductor resistance
Conductor resistance
(20°C)
Ω/km
Insulation resistance
Insulation resistance
MΩ・km
Withstand voltage
Withstand voltage
(in water) V/minute
(in water)
V/minute
Reference value
Reference value
Nominal cross-
section area
Nominal cross-section area
mm2
Configuration
No. of wires / Single wire diameter
Configuration No. of wires /
Single wire diameter

Wires /mm
Wires/mm
Outer diameter
Outer diametermm
Maximum
permissible current
Maximum permissible current
(30°C) A
Approximate
weight
Approximate weight
kg/km
Standard
Length
Standard length
m
AC TA (20°C) (60°C)
0.5 20/0.18 0.9 0.8 2.5 36.7 38.7 50 0.2 2,000 9 (11) 11 200
0.75 30/0.18 1.1 0.8 2.7 24.4 25.8 50 0.2 12 (14) 14 200
1.25 50/0.18 1.5 0.8 3.1 14.7 15.5 50 0.2 16 (19) 21 200
2 37/0.26 1.8 0.8 3.4 9.50 9.91 50 0.15 22 (25) 27 200
3.5 45/0.32 2.5 0.8 4.1 5.09 5.38 50 0.15 32 (38) 47 100
5.5 70/0.32 3.1 1.0 5.1 3.27 3.46 50 0.15 44 (51) 68 100
8 50/0.45 3.7 1.2 6.1 2.32 2.45 50 0.15 56 (66) 100 100
14 88/0.45 4.9 1.4 7.7 1.32 1.39 40 0.1 83 (96) 167 100
  • Because the 0.5 mm² size is not prescribed in the Electrical Appliances and Materials Safety Act or JIS, these products are equivalent to KIV and the surface marking is different.onambaONAMBA calendar year
  • KIV has no plating on the conductor (AC). HKIV uses plating on the conductor (TA).
  • Maximum permissible current references the maximum permissible current of indoor wiring regulation 1340-2 cables and other sources. Figures in ( ) are HKIV maximum permissible current.

 

Product Information

Feel free to contact us for more information aboutour company, products, and track record.

Contact Us
TOP >